The moulded case circuit breaker will provide protection for the circuit and equipment in case of overload.short circuit and under voltage condition occurred in the power distribution circuit. Besides, it can alsoprovide protection of overload, short circuit and under voltage for the nonfrequent start of motor.
Function (Moulded Case Circuit Breaker)
1.Overload Protection.
2.Electrical Fault Protection against short circuit currents.
3.Electrical Switch for disconnection.
QYM2 Series (MCCB)
Technical Parameters
Model: QYM2
Place of Origin: Zhejiang China
Brand Name: JOYELEC
Compliant standards: IEC 60947-2
Rated curent: 32A 40A 50A 63A 80A 100A 125A,160A,200A ,250A 320A,400A,630A,800A,1000A,1250A,1600A,2000A;
Rated voltage: 220V/230V/240V, 380V/400V/415V, 500V ,69OV
Frequency: 50/60Hz;
Thermal magnetic release: B, C, D;
Number of poles: 4P
Mechanical life: 20000 cycles;
Electrical life: 10000 cycles;
Rated short-circuit breaking capacity(lcu): 25KA,35KA,50KA,75KA( 220V/230V/240V)
Short-circuit breaking capacity (lcs): 18KA,25KA,35KA,50KA( 220V/230V/240V)
Rated insulation voltage Ui: 800V
Rated impulse withstand voltage (Uimp): 8kV
Nameplate Interpretation
Product type: Frame size, breaking capacity, poles number
Ui: Rated insulation voltage
Frequency of A.C.
Uimp: Rated impulsive withstand voltage
Ue: Rated operational voltage The product is in conformity with standard lEC/EN 60947.2
lcu/lcs: Ultimate short circuit breaking capacity/Service short circuit breaking capacity
+40'℃ : Ambient temperature Electrical symbol for circuit breaker with isolating function
Cat A: Utilization category of breaker
In: Rated operational current
li: 10ln Multiple of current of transient behavior
The product is in conformity with standard IEC/EN 60947-2